When a fault occurs,
where does current go?
Choose a familiar situation and follow the current back to its source. Compare what happens with a working protective path and when protection is missing.
Show a client what changes.
Normal current returns through neutral. The protective wire is available if a fault occurs.
What should your client remember?
Fault current needs a return circuit to its source. Earthing and bonding provide protective paths; correctly selected protective devices must disconnect the affected circuit. A ground electrode alone does not prove safety.
Request the product catalogueRead the result correctly
TN-S uses the illustrative relationship I = 230/Zs. TT uses I = 230/(RA + RB), with an assumed source electrode RB = 20 Ω and other impedances omitted. These are teaching assumptions, not site values. A B16 magnetic band is not a complete disconnection-time assessment.
TT RCD behavior is a simplified residual-current illustration. Actual selection and testing must consider the full installation, RCD type, characteristic, permitted touch voltage and disconnection requirements. Schneider Electric: TT principle · TN principle.